List of Faults and Alarms
Faults and Alarms
3-613
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
F07082 Macro: Execution not possible
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The macro cannot be executed.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex:
cccc = preliminary parameter number, bb = supplementary information, aa = fault cause
Fault causes for the trigger parameter itself:
-19: Called file is not valid for the trigger parameter.
-20: Called file is not valid for parameter 15.
-21: Called file is not valid for parameter 700.
-22: Called file is not valid for parameter 1000.
-23: Called file is not valid for parameter 1500.
-24: Data type of a TAG is incorrect (e.g.: Index, number or bit is not U16).
Fault causes for the parameters to be set:
-25: Error level has an undefined value.
-26: Mode has an undefined value.
-27: A value was entered as string in the tag value that is not "DEFAULT".
-31: Entered drive object type unknown.
-32: A device was not able to be found for the determined drive object number.
-34: A trigger parameter was recursively called.
-35: It is not permissible to write to the parameter via macro.
-36: Check, writing to a parameter unsuccessful, parameter can only be read, not available, incorrect data type, value
range or assignment incorrect.
-37: Source parameter for a BICO interconnection was not able to be determined.
-38: An index was set for a non-indexed (or CDS-dependent) parameter.
-39: No index was set for an indexed parameter.
-41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN.
-42: A value not equal to 0 or 1 was set for a BitOperation.
-43: Reading the parameter to be changed by the BitOperation was unsuccessful.
-51: Factory setting for DEVICE may only be executed on the DEVICE.
-61: The setting of a value was unsuccessful.
Remedy: - check the parameter involved.
- check the macro file and BICO interconnection.
See also: p0700, p1000, p1500
F07083 Macro: ACX file not found
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The ACX file (macro) to be executed was not able to be found in the appropriate directory.
Fault value (r0949, interpret decimal):
Parameter number with which the execution was started.
See also: p0700, p1000, p1500
Remedy: - check whether the file is saved in the appropriate directory on the memory card.
F07084 Macro: Condition for WaitUntil not fulfilled
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The WaitUntil condition set in the macro was not fulfilled in a certain number of attempts.
Fault value (r0949, interpret decimal):
Parameter number for which the condition was set.
Remedy: Check and correct the conditions for the WaitUntil loop.