Description: Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency: Refer to: p0650
Refer to: A01590
Note: For p0651 = 0, the operating hours counter is disabled.
The operating hours counter only runs for DDS0 and DDS1 (Drive Data Set).
Description: Sets the command source.
Value: 2: Terminals
Note: With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
Description: Sets the command source.
Value: 2: Terminals
6: Fieldbus
Note: With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
Description: Sets the command source.
Value: 2: Terminals
6: Fieldbus
Note: With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
p0651[0...n] Motor operating hours maintenance interval / Mot t_op maint
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Data set: MDS
Min Max Factory setting
0 [h] 150000 [h] 0 [h]
p0700[0...n] Command source selection / Cmd src sel
CU230P-2 CAN Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
2 2 2
p0700[0...n] Command source selection / Cmd src sel
CU230P-2 DP Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
2 6 6
p0700[0...n] Command source selection / Cmd src sel
CU230P-2 HVAC Access level: 1 Calculated: - Data type: Integer16
Can be changed: C(1), T Scaling: - Data set: CDS, p0170
Min Max Factory setting
2 6 2