SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Fig. 2-58 2634 – Sequence control - Missing enable signals
- 2634 -
Function diagram
87654321
FP_2634_97_51.vsd
Internal control/status words
G120 CU230P-2
29.10.2009 V4.3
Sequence control - Missing enable signals
[3060.2]
[3060.4]
[3070.2]
[3070.4]
1
0
2
3
4
...
10
11
12
...
16
17
18
19
20
21
...
...
30
31
r0046.0
r0046.1
r0046.2
r0046.3
r0046.4
r0046.10
r0046.11
r0046.12
r0046.16
r0046.17
r0046.18
r0046.19
r0046.20
r0046.
r0046.
r0046.
r0046.30
r0046.31
1
1
Missing enable signals (r0046)
Bit No.
Missing enable sig
r0046
r0046
1 = OFF1 enable missing
1 = OFF2 enable missing
1 = OFF3 enable missing
1 = Operation enable missing
1 = DC current brake, enable missing
1 = Ramp-function generator enable missing
Reserved
1 = Ramp-function generator start missing
1 = Setpoint enable missing
Reserved
1 = OFF1 enable internal missing
1 = OFF2 enable internal missing
1 = OFF3 enable internal missing
1 = Pulse enable internal missing
1 = DC current brake, internal enable missing
1 = PU enable missing
1 = Function Bypass active
1 = Drive inactive or not operational
1 = Demagnetizing not completed
1 = Speed controller inhibited
1 = Jog setpoint active
Reserved
Reserved
r0046.21
25
26
27
25
26
27
[3020.5]
0 = Internal fast stop
[3060.2]
[3070.2]
1 = Internal RFG enable
Fault with OFF3 response