Siemens CU230P-2 DP - p1035[0...n] BI: Motorized potentiometer setpoint raise; Mop raise; p1036[0...n] BI: Motorized potentiometer lower setpoint; Mop lower; p1037[0...n] Motorized potentiometer maximum speed; Mop n_max; p1038[0...n] Motorized potentiometer minimum speed; Mop n_min

Siemens CU230P-2 DP
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-130
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description: Sets the signal source to increase the setpoint for the motorized potentiometer
Dependency: Refer to: p1036
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to reduce the setpoint for the motorized potentiometer.
Dependency: Refer to: p1035
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source to reduce the setpoint for the motorized potentiometer.
Dependency: Refer to: p1035
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the maximum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description: Sets the minimum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
p1035[0...n] BI: Motorized potentiometer setpoint raise / Mop raise
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.13
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
CU230P-2 CAN
CU230P-2 HVAC
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 0
p1036[0...n] BI: Motorized potentiometer lower setpoint / Mop lower
CU230P-2 DP Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Data set: CDS, p0170
Min Max Factory setting
- - 2090.14
p1037[0...n] Motorized potentiometer maximum speed / Mop n_max
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1038[0...n] Motorized potentiometer minimum speed / Mop n_min
Access level: 3 Calculated: p0340 = 1,3,5 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]