Parameters
Quick commissioning (p0010 = 1)
1-432
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
*) This function will be realised in next FW version.
When p0010 = 1 is chosen, p0003 (user access level) can be used to select the parameters
to be accessed.
At the end of the quick commissioning sequence, set p3900 = 1 to carry out the necessary
motor calculations and clear all other parameters (not included in p0010 = 1) to their default
settings.
p1000 Selecting the speed setpoint 1 C(1)T
p1080 Minimum speed 1 C(1)T
p1082 Maximum speed 1 C(1)T
p1120 Ramp-function generator ramp-up time 1 C(1)UT
p1121 Ramp-function generator ramp-down time 1 C(1)UT
p1135 OFF3 ramp-down time 2 C(1)UT
p1300 Open-loop/closed-loop control operating mode 2 C(1)T
p1500 Selecting the torque setpoint 2 C(1)T
p1900 Motor data identification and rotating
measurement
1 C(1)T
p3900 Completion of quick commissioning 1 C(1)
Note
This applies only in Quick Commissioning mode.
Table 1-4 Quick commissioning (p0010 = 1), Fortsetzung
Par.-No. Name Access level Can be
changed