Push the four latches outward (see arrows).
Fasten the four captive screws in the sequence printed on the heat sink (1 to
4), by proceeding as follows:
T
orque: 0.9 Nm (not used in Japan)
First, fasten the captive screws 1 and 2 completely
.
Fasten the captive screws 3 and 4 completely.
Proceed for the second LC heat sink in the same way.
Note when tightening the screws of the CPU heat sink:
As shown in the figure below, tighten the screws while checking the screw
tip until it is visible through the screw hole.
When you reach the above position, hold the screw driver with two fingers
and tighten the screw firmly.
Liquid cooling (LC)
380 Upgrade and Maintenance Manual RX2540 M6