Page 146 Chapter 2 Installing SmartPAC 2 and WPC
If the LED is blank or shows some other error, check and correct the wiring. After
you correct the problem, run the test again, starting from step 2. If the ram still does
not make a stroke or does not stop at top dead center, contact Wintriss Tech Support.
5. Change to INCH mode and bring the ram to top dead center.
6. Momentarily press and then release the RUN/INCH buttons. The ram should start, then
stop. The INTERRUPTED STROKE message should flash on the display and the press
should now be in the TWO HAND MAINTAINED SINGLE STROKE mode.
If the press behaves as indicated above, go to the next step.
If the press behaves differently, check the wiring and repeat the test described in this
step. If, after you have corrected the wiring, the press still behaves differently,
contact Wintriss Tech Support for assistance.
7. Since the press is now in TWO HAND MAINTAINED SINGLE STROKE mode,
complete the stroke by pressing and holding the RUN/INCH buttons.
Go to the next applicable test.