Page 374 Chapter 6 SmartPAC 2 Run Mode
Setting Prior Act Timing for Automatic Single Stroke
For automatic single stroke mode, use option switch 5 to select 30 seconds or 5 minutes for
the prior act timing. (See “Switch 5 – Prior Act Timing for Automatic Single Stroke and
Continuous on Demand,” page 245.)
Inside the unit, use option switch 5 to set prior act timing for Automatic Single Stroke mode,
as follows:
Option Switch 5 Setting
Prior Act Timing for
Automatic Single Stroke
OPEN 30 seconds
CLOSED 5 minutes
Automatic Single Stroke Operating Instructions
After you have correctly installed sensors or other components required for Automatic Single
Stroke, set the switches as follows:
• Select TWO HAND the mode select menu (page 365).
• Stroke select to SINGLE STROKE
• Automatic single stroke switch according to the timing you want (see previous
section).
To initiate the first stroke:
1. Depress the PRIOR ACT button. The prior act button will blink when PRIOR ACT is
armed.
2. Press the RUN/INCH buttons until the ram passes bottom dead center.
The up stroke and all other strokes will be automatic.
It is not unusual for the press to pause at top stop. It is waiting for the "go" signal from the
external switch.
The external signal must occur after top stop within the time set with switch 5 (30 seconds or
5 minutes). If WPC does not receive the signal within this amount of time, it assumes a
problem has occurred and will not start the next stroke. If this happens, repeat steps 1 and 2
to re-initiate.