SmartPAC 2 with WPC Integration 1126800
Installing SmartPAC 2 and WPC Chapter 2 page 31
insert wire here
tighten screw to clamp
wire in terminal
Figure 2 - 2. Attaching Wires to Connector
How to Terminate Cable Shields
NOTICE
TERMINATE BOTH ENDS OF SHIELD
Be sure to terminate the cable shields at both ends (for example, at SmartPAC 2 and DSI 2).
Your Wintriss units have ground studs on the inside of the enclosure for terminating cable
shields at the point of entry.
Secure drain wire
under nut on
ground stud
Drain wire
Strip cable jacket
as far as end of
conduit fitting
Figure 2 - 3. Connecting Shield Drain Wire to Ground Stud
For each shielded cable, perform the following steps. Refer to the figure above.
1. Strip the cable jacket as far as the end of the conduit fitting.
2. Cut the drain wire to a length that can wrap at least once around the nearest ground stud.
Loosen the nut on the stud, wrap the drain wire around clockwise and tighten the nut.
3. Connect the rest of the wires in the cable to the terminal block as appropriate.