SmartPAC 2 with WPC Integration 1126800
SmartPAC 2 Initialization Mode Chapter 4 page 245
Switch 5 – Prior Act Timing for Automatic Single Stroke and Continuous on
Demand
NOTICE
After you change switch settings, power down the SmartPAC 2/WPC. Power it up again to
enable the new settings. If you do not this, the previous switch settings will remain in effect.
Option Switch 5 sets the prior act timing for Automatic Single Stroke mode and for
Continuous on Demand mode. The switch in the OPEN position selects the shorter prior act
time for both modes (30 seconds/1 minute, respectively). The switch in the CLOSED
position selects the longer prior act time for both modes (5 minutes/10 minutes, respectively).
Refer to the table below .
For more information about Automatic Single Stroke mode, see “Operating the Press in
Automatic Single Stroke Mode,” page 373. For more information about Continuous on
Demand mode, see “Operating the Press in Continuous on Demand,” page 377.
Set Switch 5 in the Press Control Option Switches screen, Figure 4 - 33, page 241.
Table 4 - 8. Switch 5 Setting for Prior Act Timing
Option Switch 5 Setting
Prior Act Timing for
Automatic Single Stroke
Prior Act Timing for
Continuous on Demand
OPEN 30 seconds 1 minute
CLOSED 3 minutes 10 minutes