SmartPAC 2 Fault Messages Chapter 7 page 417
"The resolver position is different from when the unit was turned off"
Explanation: This message will only appear if SmartPAC 2 detects a different resolver
angle position from the time that the press was turned off to when it was
turned on again. This can happen when you move the press or upgraded
SmartPAC 2 firmware.
Remedy: Press RESET to clear. If the message reappears, contact Wintriss Tech
Support.
“One of the sensor auto enable counters is greater than 24”
Explanation: Normally this fault will not ever occur since SmartPAC 2 does not let you
enter a value greater than 24. However, it could appear if there is a
problem with the internal workings of SmartPAC 2.
Remedy: First press RESET. If the message reappears, contact Wintriss Tech
Support.
“Loss of Communication at Address X”
Explanation: SmartPAC 2 detects that it cannot communicate with one of the option
modules. “X” refers to one of the addresses shown in the table below.
Remedy: Check the wiring the module affected. If you continue to get the error
message contact Wintriss Tech Support.
Message Refers to Option
Loss of Communication at Address 1
AutoSetPAC or WaveFormPAC
Channels 1 - 4
Loss of Communication at Address 2
AutoSet or WaveFormPAC
Channels 5 - 8
Loss of Communication at Address 4 RamPAC
Loss of Communication at Address 5 ProPAC