SmartPAC 2 with WPC Integration 1126800
SmartPAC 2 Fault Messages Chapter 7 page 425
more pins are bent and not plugged in properly. If the unit still malfunctions, contact
Wintriss Tech Support for assistance.
DANGER!
INCORRECT STOP TIME LIMIT AFTER INITIALIZATION
Determine the stopping time and set the Stop Time Limit at a value based on the actual
stopping time of your press whenever you initialize your WPC. Use the stop time measured
in the 90° stop time test to calculate the safety distance. When you initialize your WPC the
stop time limit is reset to its factory setting of 500 ms.
Failure to comply with these instructions will result in death or serious injury.
12. Re-initialize the system according to the instructions in Chapter 2, “Initialize Press
Parameters,” page 101. Then re-enter the WPC setting values you recorded before
replacing the chips. Perform the installation verification tests and final checkout tests in
Chapter 2 before operating the press.