4 Use the [0 to 9] keys to assign the format code (for example, 0420 ADEMCO Contact
ID format.
5 Press
/ .
6 Press
/ again followed by the key to return to the previous level.
NOTE:
For SIA and Contact ID formats, refer to Dialer: Auto Codes, page 132.
7 Access and configure the parameters in the Communication Format menu, as follows:
Dialer: Communication Format
Quick Keys Parameter Default
55
33
11
Format for MS Tel No. 1
0000
1. Defines the protocol format for the first MS telephone number.
2. Type in the 4-digit Format Code that corresponds to the communication
protocol for the
MS Receiver connected to the first MS Telephone
Number.
3. Toggle to access the [0 to 9] keys using the
/ or
/ keys.
4. Press
/ .
55
33
22
Format for MS Tel No. 2
0000
Defines the protocol format for the second MS telephone number.
Same as the option described above, except for the receiver connected to the
second MS Telephone Number.
55
33
33
Format for MS Tel No. 3
0000
Defines the protocol format for the third MS telephone number.
Same as the option described above, except for the receiver connected to the
third MS Telephone Number.
Monitoring Station (MS) Communication Formats
Protocols Communication Formats Format
Code
Most Common Protocols:
ADEMCO Contact (Point) ID DTMF, Parity 0420
SIA Level 0700
Simple Pulse Protocols:
Silent Knight/ADEMCO Slow 010F
Silent Knight/ADEMCO Slow-Extended 014F
Radionics/DCI/Franklin Slow 0117
Silent Knight Fast 010E
Silent Knight Fast-Extended 014E

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Risco ProSYS series and is the answer not in the manual?

Risco ProSYS series Specifications

General IconGeneral
CommunicationIP, GSM, PSTN
Wireless ProtocolTwo-way wireless
Battery BackupYes
Remote ControlYes, via app
IntegrationRISCO Cloud

Related product manuals