ProSYS Installation and Programming Manual 89
Zones Miscellaneous: BUS Zone – iWISE QUAD Grade 2
Quick Keys Parameter Default Range
22
00
33
ZZZZ
11 LEDS
On
Defines the LEDS operation mode.
[1] Off - Disables the LEDS operation.
[2] On – Enables the LEDS operation.
22
00
33
ZZZZ
22 Sensitivity
High
Defines the sensitivity of the detector (PIR).
[1] Low [2] High
22
00
33
ZZZZ
33 Self Test
Remote
Used to test detection technologies. In the event of a failed test, a Self Test
Trouble is created.
[1] Remote (manual) - Performed by the system when a user manually selects
the Diagnostics option from the Maintenance menu via the ProSYS User
Functions menu.
[2] Local (automatic) - Once an hour, the detector automatically checks that the
detector’s channels are functioning properly.
Zones Miscellaneous: BUS Zone – iWISE QUAD Grade 3
Quick Keys Parameter Default Range
22
00
33
ZZZZ
11 LEDS
On
Defines the LEDS operation mode.
[1] Off - Disables the LEDS operation.
[2] On – Enables the LEDS operation.
22
00
33
ZZZZ
22 Sensitivity
High
Defines the sensitivity of the detector (PIR).
[1] Low [2] High
22
00
33
ZZZZ
33
Anti-Mask
Enable
Defines the operation of Anti Masking detection.
[1] Disable [2] Enable and behaves according to the settings defined in quick
keys [2][0][3][zz][4]
22
00
33
ZZZZ
44 Arm/Disarm
No
Defines the operation of the anti masking detection while the detector is armed
or disarmed
[1] No – While armed or disarmed, anti-mask behaves according to the setting
defined in quick keys [2][0][3][zz][3] above.
[2] Yes – While armed, anti-mask is disabled. While detector is disarmed Anti-
mask behaves according to the settings defined in quick keys [2][0][3][zz][3].