ProSYS Installation and Programming Manual 47
3 Access and configure the parameters in the Time Define menu, as follows:
System: Time Define
Quick Keys Parameter Default Range
11
11
11
Exit/Entry Delay 1
Exit/Entry Delays (Group 1).
11
11
11
11
Entry Delay 1
30 seconds 0-255 seconds
Duration of Group 1 Entry Delay.
Note:
For SIA CP 01 installations the range of entry time should be between 30 to 240
seconds with default of 30 seconds.
11
11
11
22
Exit Delay 1
45 seconds 0-255 seconds
Duration of Group 1 Exit Delay.
Note:
For SIA CP 01 installations the range of exit time should be between 45 to 255
seconds with default of 60 seconds.
11
11
22
Exit/Entry Delay 2
Exit/Entry Delays (Group 2).
11
11
22
11
Entry Delay 2
45 seconds 0-255 seconds
Duration of Group 2 Entry Delay.
Note:
For SIA CP 01 installations the range of entry time should be between 30 to 240
seconds with default of 30 seconds.
11
11
22
22
Exit Delay 2
60 seconds 0-255 seconds
Duration of Group 2 Exit Delay.
Note:
For SIA CP 01 installations the range of exit time should be between 45 to 255
seconds with default of 60 seconds.
11
11
33
Bell Timeout
04 minutes 01-90 minutes
Duration of the external siren(s) during alarm.
11
11
44
Bell Delay
00 minutes 00-90 min. /sec.
The time delay before the keypad siren and the external siren operates after
the onset of an alarm.
11
11
55
Switched Auxiliary Break
10 seconds 01-90 seconds
The time that the power supplied to the system's smoke detectors through the
Utility Output is interrupted during a user-initiated smoke detector reset,
typically performed after a Fire Alarm or automatically when a fire verification
is defined in the system control. (Refer to Double Verification of Fire Alarms,
page 50, for additional details.)
NOTE:
This feature is supported through any Utility Output that is defined as Switch AUX.