28 ProSYS Installation and Programming Manual
Jumpers Po
siti
on
Function
UO1 (J10)
Determines the UO1 connection (behavior), see
Connecting the J10 Connector, page 25.
Default: 1 PIN
Connectors
Connector Function
J1, J5
BUS 1 Plug in connector.
J8
BUS 2 Plug in connector.
J4
SIG In connector. The J4 SIG IN voice connector enables the
transfer of audio data between the Voice module RP200VC and
the phone line.
J6
The J6 connector is used to connect the Advanced Digital Voice
Module (rp128ev00uka) to the ProSYS.
Connect the Voice module to the VOICE connector (J6) on the
Main Panel via the supplied cable. This connector transmits
signals from the Voice module to the telephone line during remote
communication and is essential for normal operation of the Voice
module.
Connecting AC Power
 To connect AC power:
1 Connect the 230V AC to the mains fuse (SLOW BLOW 315 mA) input terminal block
according to the Local National Electronic Code.
2 Fasten the AC cord to the metal box using adjustable clamps.
!
IMPORTANT:
Do NOT apply mains power at this time.
Be sure to connect the live wire of the AC power through the AC fuse. The size of the conductors
must not be less than 0.75mm
2
(18AWG).