ProSYS Installation and Programming Manual 193
Maintenance
Quick Keys Parameter Range
44
11
Keypad Text
This parameter momentarily tests the keypad indicators and the
system's external sounder(s).
44
22
Battery Test
This parameter tests the system’s standby batteries.
44
99
Diagnostics
This menu enables performing diagnostic tests for:
[1] BUS Zones
[2] Power Supply
[3] Siren
[4] GSM
44
00
More
The More menu provides additional parameters.
1. From the Maintenance menu, press [0] and press
/ .
The following display appears.
MAINTENANCE:
1)WALK TEST
2. Access and program the parameters as follows:
44
00
11
Walk Test
The walk test enables the installer or the Grand Master to easily test
and evaluate the operation of each zone in the system.
NOTE:
The difference between performing a walk test with an installer code compared to
using the Grand Master code relates to a tamper condition. A tamper during a
Grand Master Walk Test will cause an alarm in the system while; a tamper during
an Installer Walk Test will only cause a message display.
1. Make sure the system is disarmed.
2. Select [1] Walk Test. A beep is heard and the following display
appears.
MAKE WALK TEST
AND HIT ANY KEY
Walk throughout the protected area and make sure you test
every zone in the system.
3. When done press any key. A list with the tripped zones during
the walk test appears.
4. Press
/
to confirm and exit the walk test mode.