Engineering data (equipment properties)
Number of units 50
Number of materials 100
Number of qualities per material 2
Recipe data
To calculate the performance data, a hierarchical recipe with the following characteristic data
is used.
Configured recipe data in the BATCH Control Center:
Number of RUPs per RP 10
Number of ROPs per RUP 10
Number of RPHs per ROP 15
Number of RPHs in simultaneous branches 5
Number of transitions per ROP 15
Number of conditions per transition 5
Number of header parameters per recipe / formula 100 / 10
Number of parameters per RPH 15
Number of parameters per control strategy 10
Number of active RUPs per RP 3
Number of process tags per RUP 5
Number of process tags per ROP 3
Number of configured electronic signatures (ESIG) in an RP 3
Number of of active RPHs within a batch 3
Batch data
Number of planned batches 100
Number of batches per order 100
Number of batches to be created simultaneously 100
Number of released batches 100
Number of batches to be released simultaneously 100
Number of batches running simultaneously 100
Number of of active RPHs within a batch 3 PC-based
30 AS-based
Number of of active RPHs within a batch process cell 30 PC-based
350 AS-based
Number of opened batches (control recipes) on all BATCH clients 30
Number of batches to be completed simultaneously 50
Number of batches to be archived simultaneously 30
Number of batches to be deleted simultaneously 30
Number of active BATCH clients (BATCH Control Center) 5
Product introduction and installation
3.6 Configuration limits
SIMATIC BATCH V8.2
70 Operating Manual, 02/2016, A5E35958174-AA