CAUTION
CPUs are extremely sensitive to electrostatic discharge and therefore
must always be handled with care.
After a CPU has been removed from its protective sleeve or from its
socket, place it upside down on a nonconducting, antistatic surface.
Never push a CPU over a surface.
Preliminary steps
"Locating the defective server" on page 49.
"Suspending BitLocker functionality" on page
87.
"Shutting down the server" on page 52.
"Disconnecting the power cord" on page 53.
"Getting access to the component" on page 56.
"Removing the air duct" on page 78.
If applicable, remove the riser module, see "Removing the riser module 1"
on page 70.
Removing the LC kit
Remove the cross bar, see "Removing the cross bar" on page 80.
Liquid cooling (LC)
370 Upgrade and Maintenance Manual RX2540 M6