1126800 SmartPAC 2 with WPC Integration
Page 396 Chapter 7 SmartPAC 2 Fault Messages
25
Problem: This error is related to the flywheel motion monitoring option. When you
see this error, it means that WPC does not detect that the position sensor
installed on the flywheel has turned on or off when the flywheel is turning.
Remedy: After clearing the error, check the installation and wiring of the position
sensor. If you wish to disable this feature, set the flywheel timer to a
value of 0 (zero). Refer to the section "Setting Shutdown and Flywheel
Timer Limits" in Chapter 4 for more information.
26
Problem: This means that the flywheel turned too fast, potentially creating an unsafe
barring condition (more than an equivalent of 6 SPM) while the press was
in Bar mode.
Remedy: After clearing the error, bar the press more slowly.
28
Problem: This means that the flywheel was still in motion when the motor was
started in the opposite direction, or when Bar mode was selected.
Remedy: Reset and wait until the flywheel stops turning. If the number of seconds
set at "Spin down time" in Initialization is too long, adjust as necessary.
See Chapter 4 for a description of this option.