365-575-102 Circuit Order: NTP-010
Issue 8.0, July 2002 Page 3 of 6
Supplemental Information: If an incoming
OC3/IS-3 LOS condition exists prior to setting the
Alarm Level to NO, this condition will not
disappear after the Alarm Level is set to NO. Only
subsequent conditions will be subdued (not
reported). The user may clear the condition by
temporarily providing a good input signal until the
condition clears or by reseating the OC3/IS-3
circuit pack. Only reseat the circuit pack if you are
sure there is no live traffic on the outgoing fiber,
otherwise service interruption will occur.
4. At the CIT, select
CONFIGURATION-Retrieve-Equipment,then
LS INTFC and execute to obtain an Equipage and
Version Report.
—
5. Determine from the report if the OC-3 circuit pack is
already present in the slot associated with an OC-3
circuit pack to be added. A circuit pack is in the slot
if OC3 is indicated in the Circuit Pack column of
the report.
If an OC3 circuit pack(s) is present in the
slot(s), then continue with Step 11.
If there is no circuit pack(s) present in the
slot(s), then continue with Step 6.
If any circuit pack(s) other than OC3 is
present in the slot(s), remove the circuit
pack(s), perform a CONFIGURATION-
Update command and continue with Step 6.
6. Remove the appropriate low-speed shelf cover. DLP-511
7. If necessary, remove the apparatus (circuit pack)
blank(s) from the slot(s) requiring new circuit
pack(s).
DLP-533
8. Install OC-3/IS-3 circuit pack(s) into the specified
slot(s) of the low-speed shelf [with the appropriate
receive lightguide buildouts (LBOs)] and then
connect the optical fibers per the circuit order.
DLP-514
DO ITEMS BELOW IN ORDER LISTED . . . . . . . . FOR DETAILS, GO TO