365-575-102 TroubleClearing:
Issue 8.0, July 2002 Page 1 of 2
TAP-152
Clear ‘Inc. (from OC48) Sync Ref Fail’
NOTE:
An "inc. (from OC48) sync ref fail" condition is associated with
another condition that prevents the TG circuit pack from receiving a good
synchronization reference signal from the associated RCVR circuit pack.
1. Does an "incoming OC-48 LOS," "RCVR failure," or "RVCR removed" condi-
tion also appear in the Active Alarms and Status Report on the CIT screen?
If YES, then find that condition in Table A of TAP-102 and go to the indi-
cated Trouble Clearing procedure.
If NO, then go to TAP-108.
2. STOP! YOU HAVE COMPLETED THIS PROCEDURE.