365-575-102 TroubleClearing:
Issue 8.0, July 2002 Page 1 of 2
TAP-157
Clear ‘FT-LBA (Condition)’
Overview: This procedure is used to clear a condition at an FT-2000 Lightwave
Booster Amplifier (FT-LBA) in response to one of these indicated conditions at the
FT-2000 network element:
FT-LBA fan failure FT-LBA fuse/power failure
FT-LBA 1EW failure FT-LBA 1WE failure
1. Are you responsible for maintaining the FT-LBA?
If YES, then continue with Step 2.
If NO, then STOP! YOU HAVE COMPLETED THIS PROCEDURE.
2. Clear the FT-LBA trouble condition(s) by using the FT-LBA user documentation
(365-565-500).
3. To verify that the trouble condition has been cleared, select
FAULT-Retrieve-Alarm at the CIT to obtain an Active Alarms and Status
Report from the FT-2000 network element and verify the condition is not
shown.
4. STOP! YOU HAVE COMPLETED THIS PROCEDURE.