DLP-500: Detailed Level Procedure 365-575-102
Page2of4 Issue8.0,July2002
!
WARNING:
Unterminated optical connectors may emit invisible laser radiation. Eye
damage may occur if a beam is viewed directly or with improper optical
instruments. Avoid direct exposure to the beam
!
CAUTION:
A wrong connection can be avoided by marking or recording all
disconnections in Steps 3, 4, and 5.
3. Remove the optical OC-48 line connection from the OUT connector of the
TRMTR circuit pack and slide the protector cap (if available) over the end of
the fiber.
4. Remove the optical OC-48 line connection to the IN connector of the RCVR
circuit pack and slide the protector cap (if available) over the end of the fiber.
5. Remove the lightguide buildout from the IN connector of the RCVR circuit
pack, if equipped.
Reference: DLP-512
Table A Lightguide Buildout Values
dB Loss Letter Code
5 ±1B
10 ±1D
15 ±2F
20 ±2H
Table B - Lightguide Buildouts and Circuit Pack
Compatibility
Buildout Type (Code) Circuit Pack
ST
â
(A3010*), FC(A3030*) TRMTR 739B1
TRMTR 739C1
RCVR 839B1
ST
(A3070*),FC(A3080*),
or SC (A3060*)
TRMTR 739B2/B5
TRMTR 739C2/C5
TRMTR 739J2/J5
TRMTR 739J3
TRMTR 739P5
TRMTR 739R2/R5
TRMTR 739S2/S5
TRMTR 739E_
RCVR 839B2/B4/B5
* See Table A for letter code.