365-575-102 DetailedLevelProcedure:
Issue 8.0, July 2002 Page 1 of 2
DLP-513
Test Fan Assembly (ED-6G992-30)
1. Observe that the POWER ON LED is lighted and the ALM LED is off at the fan
assembly. If another condition exists, notify the group that installed the fan
assembly.
2. Press and hold in the ALM TEST pushbutton for 20 seconds or until the fan
speed slows down sufficiently to cause the control board to activate the fan
alarm.
Response: POWER ON and ALM LEDs should be lighted while ALM TEST
pushbutton is depressed.
3. Release ALM TEST pushbutton.
Response: POWER ON LED should be lighted and ALM LED should be off.
4. At the CIT, select FAULT-Retrieve-History to obtain a Maintenance History
Report.
5. Are "fan failure" and "fan failure - cleared" conditions listed for the time the fan
assembly was tested?
If YES, then STOP! YOU HAVE COMPLETED THIS PROCEDURE.
If NO, then refer the provisioning discrepancy to the group that did instal-
lation of the fan assembly.
Reference: The CONFIGURATION-Set-Attribute-Environment
command in Chapter 8 provides information on provisioning
the miscellaneous discrete input points #16 as "fan failure."