EasyManua.ls Logo

Lucent Technologies FT-2000 OC-48 - Page 983

Lucent Technologies FT-2000 OC-48
1578 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
365-575-102 Acceptance: NTP-011
Issue 8.0, July 2002 Page 3 of 4
Acceptance: NTP-011---+---TAD-100
|---365-575-115
|---365-565-500
|---Acceptance: NTP-007
|---DLP-501
At the FT-LBA, remove the 10A fuse from
the -48A fuse socket on the user panel.
6. At the CIT, select FAULT-Retrieve-Alarm
command to obtain an Active Alarm and Status
Report. An example of this report with a
description of the output parameters is provided
in Section 11 of this manual.
7. From the report, verify the correct condition is
listed in the Description column of the report.
(Your report may include only one condition at a
time.) If the condition does not appear, notify
the installation group of the problem.
FT-LBA fuse/power failure
FT-LBA 1WE failure
FT-LBA 1EW failure
FT-LBA fan failure
8. Repeat Steps 5 through 7 for each of the
miscellaneous discretes listed below.
Remove the 10A fuse from the -48B fuse socket
at the FT-LBA,
Disconnect the 1EW fiber at the FT-LBA,
Disconnect the 1WE fiber at the FT-LBA.
9. STOP! YOU HAVE COMPLETED THIS
PROCEDURE.
DOITEMSBELOWINORDERLISTED....... FORDETAILS,GOTO

Table of Contents