High limit
(not applicable for data
types Boolean, String,
and user data type)
The high limit of the setpoint is specified here.
Low limit (not applicable
for data types Boolean,
String, and user data
type)
The low limit of the setpoint is specified here.
Setpoint The setpoint is specified here. In doing so, the following applies: Low limit
≤ setpoint ≤ high limit. Only valid values are allowed.
Created by Specification of the application that created the object, either SIMATIC
BATCH PCell Control Center or SIMATIC Manager:
● If a type object was created by SIMATIC Manager, additional subobjects
cannot be added, nor can the selected object be deleted or changed,
either via the PCC API or with the PCC configuration dialog.
● If an instance object was created by SIMATIC Manager, additional
subobjects can be added via the PCC API or with the PCC configuration
dialog. However, it is still not possible to delete or change the selected
object here.
"Parameters" button Activating this button takes you to the appropriate operation type parame‐
ter. Use the Back button on the operation type parameter to return to this
point.
Block
Buttons
Check validity All batch instances, starting with the selected object (here, a parameter of
an equipment operation), are checked for consistency with the batch types
and for conformity to ISA-88. The validity errors and validity warnings are
displayed in the log field and can be visualized using the "Display" button.
Update All batch instances are adapted according to the batch types. This action
is always required if a change has been made to batch types of existing
batch instances (e.g., inserting a new parameter, changing the unit of
measure, etc.).
Log
"Errors" display field The number of errors for the selected log is displayed.
"Warnings" display field The number of warnings for the selected log is displayed.
"Display" button The logging is activated with the "Display" button. The selected log is
generated as an XML file in the specified layout and displayed in In‐
ternet Explorer.
Select "Process cell" and click the "Display" button to show all process
cell errors or warnings. You can also right-click a selected object and
select the "Display log" function to display object-specific errors or
warnings.
Context help references
14.1 Dialogs
SIMATIC BATCH V8.2
1036 Operating Manual, 02/2016, A5E35958174-AA