8. Here, set the attribute "S7_tagcollect" (process tags) to "true" and the attribute "s7_m_c"
to "true". Only then will the archiving parameters be sent to the PCS 7 OS and become
available for operator control and monitoring.
9. Open the corresponding block and check if the "S7_m_c" attribute is set to "true" for the
inputs. Navigate to the appropriate inputs in the tag overview and right-click to open the
object properties. The "S7_m_c" attribute must exist in the "Attributes" tab and be set to
"true".
10.Apply the attributes with "OK".
11.Open the CFC chart and insert the function block from the "S7 Program" folder into a CFC
chart.
Result: The TAG_COLLECT FB type appears in the "Other blocks" library or in the library
of the family assigned to the FB (for example: Batch) and can be immediately used for
configuring additional process tag types.
Note
The FB type TAG_COLLECT must be stored in the library, for example under "Other Blocks"
so that the process tag types created in this way can be generated in the BATCH
configuration dialog.
12.Open the BATCH configuration dialog with the menu command Options > SIMATIC
BATCH.
13.Select the "Batch types" object in the left window.
Engineering
7.1 Basic engineering for PCS 7
SIMATIC BATCH V8.2
166 Operating Manual, 02/2016, A5E35958174-AA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC BATCH and is the answer not in the manual?

Siemens SIMATIC BATCH Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC BATCH
CategoryControl Systems
LanguageEnglish

Related product manuals