80 Pamux User’s Guide
CONFIGURE ANALOG POINT 15
PURPOSE:
Configures the position of an analog point as an input or output.
COMMAND TYPE:
Analog
PARAMETERS:
COMMAND Contains the value 15.
ADDRESS Contains the address of the Pamux brain board.
POSITION Contains the point number.
VALUE ARRAY The first element of this array contains a 0 if the point will be configured as an
input, or anything else if the point will be configured as an output.
REMARKS:
All output module positions must first be configured as outputs before values can be written to
them. The driver will ignore any write commands to positions configured as inputs and no errors
will be returned.
The POSITION value is a point offset starting from the value in the ADDRESS parameter. The point
number in the POSITION parameter can range from 0 to 511 if the ADDRESS parameter is 0. An
error will be returned if the values in these parameters exceed the limits.
EXAMPLE:
This example configures point 0 at address 1 as an output.
100 COMMAND% = 15 ‘ Configure Analog Point command
110 ADDRESS% = 1 ‘ Address of brain board
12 0 POSITION% = 0 Point number 0
130 VALUE%(0) = 1 ‘ Configure as an output
140 GOSUB 1000 ‘ Call the driver
.
.
1000 CALL
Pamux(ERRCOD%,ADDRESS%,COMMAND%,POSITION%,VALUE%(0))
1010 IF ERRCOD% < 0 THEN GOTO 2000
1020 RETURN
PROGRAMING WITH THE PAMUX DRIVER

Table of Contents

Related product manuals