For components used as main disconnect, the minimum overcurrent
ratings are:
• All 208/120-volt circuit protection devices to be rated minimum
10,000 AIC.
• All 480/277-volt circuit protection devices to be rated minimum
14,000 AIC.
Exception: Overcurrent protection devices do not require these ratings if
they are located on the load side of another overcurrent protection device
with the proper AIC rating. This overcurrent protection device must be
mounted close to the equipment.