TAP-110: Trouble Clearing 365-575-102
Page4of4 Issue8.0,July2002
7. Did the same incoming signal failure clear?
If YES, then STOP! YOU HAVE COMPLETED THIS PROCEDURE.
If NO, remove the replacement circuit pack and return the original circuit
pack to the slot, then continue with Step 8.
8.
NOTE:
At this point, it appears that the local terminal is operating correctly. The trouble
is in the line or in the far-end terminal.
Initiate a Trouble Report to the source of the failed incoming signal indicating
the type of failure. If the source of the failed incoming signal returns a Trouble
Report indicating "no trouble found," then follow the prescribed operating pro-
cedures to fault isolate the cable/fiber carrying the failed incoming signal.
Reference: DLP-535
9. STOP! YOU HAVE COMPLETED THIS PROCEDURE.