365-575-102 TroubleClearing:
Issue 8.0, July 2002 Page 1 of 2
TAP-124
Address ‘Reset in Progress’
NOTE:
A software reset is in progress. This involves downloading software from
SYSMEM to SYSCTL, to LNCTLs, and to OHCTLs and to board controllers on
all other circuit packs. This can take as long as 10 minutes. During this time,
the miscellaneous discrete control points are deactivated.
1. Is the MJ LED lighted?
If YES, then wait 10 minutes before proceeding with Step 2.
If NO, then continue with Step 5.
2. At the CIT, select FAULT-Retrieve-Alarm to obtain an updated Active
Alarm and Status Report.
3. Is reset in progress still reported?
If YES, then continue with Step 4.
If NO, then continue with Step 7.
4. Wait 10 minutes or until the MJ LED is off at the user panel.
5. At the CIT, select FAULT-Retrieve-Alarm to obtain updated Active Alarm
and Status Report.
6. Is reset in progress still reported?
If YES, then go to TAP-108.
If NO, then continue with Step 7.
7. Is the NE ACTY LED lighted?
If YES, then go to Trouble Clearing: IXL-001.
If NO, then STOP! YOU HAVE COMPLETED THIS PROCEDURE.