365-575-102 Detailed Level Procedure: DLP-515
Issue 8.0, July 2002 Page 1 of 2
Replace Fuse in Power Distribution and Fuse Panel
or User Panel
Overview: This procedure is used to replace a blown 10A fuse (red lamp is lighted)
in the power distribution and fuse panel or in the user panel.
1. Obtain a replacement 10A fuse.
2. Unsnap and lift the latch (from bottom to top) that is around the red lens cap.
3. Push in and down at the top of the red lens cap. Release slowly because the
lens cap/fuse should spring forward.
4. Remove the lens cap/fuse from the fuse socket.
5. Remove the blown 10A fuse from the lens cap/fuse and replace with the
replacement 10A fuse.
6. Install the lens cap/fuse into the fuse socket by pushing in and up at the bot-
tom of the lens cap.
7. Lower the latch (from top to bottom) around the red lens cap and snap into
place.
8. Did the alarm clear in approximately five minutes?
If NO, perform DLP-550, Replace a Defective Power-Line Filter.
If YES,gotoStep9.
9. STOP! YOU HAVE COMPLETED THIS PROCEDURE.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies FT-2000 OC-48 and is the answer not in the manual?

Lucent Technologies FT-2000 OC-48 Specifications

General IconGeneral
BrandLucent Technologies
ModelFT-2000 OC-48
CategoryNetwork Hardware
LanguageEnglish