DLP-550: Detailed Level Procedure 365-575-102
Page 8 of 16 Issue 8.0, July 2002
24. Reinstall the fuse.
Reference: DLP-515, Replace Fuse in Power Distribution and Fuse
Panel or User Panel Steps 6 and 7.
25. Did the alarm clear in approximately five minutes?
If NO,gotoOption 2: Replace the Circuitry Unit of a Power Line Filter
Assembly on page 9.
If YES,
STOP! YOU HAVE COMPLETED THIS PROCEDURE.