Motion control C3F_T40
308 192-121102 N04 June 2008
1: Area whrere a module error is generated.
2: Ignore Zone: Area whrere
no module error and no Done is generated.
The ranges 2 and 3 may not overlap. If they do, the ignore zone in range 3 is
not effective.
3: ExpectedValueZone: Trigger signal in the permissible value range; this is
confirmed with Done=TRUE.
4: RecordedSignal; is updated with every active edge of the TriggerInput signal
upon Execute = TRUE.
If the value of the signal (SignalSource) during the Trigger event is in the
permissible value range between (ExpectedValue - Tolerance) and
(ExpectedValue + Tolerance), this is confirmed with Done = TRUE; the
RecordedSignal ist updated.
If the value of the signal (SignalSource) during the Trigger Event is between
StartIgnore and StopIgnore (Ignore zone), the module will report neither error nor
Done, the RecordedSignal is however updated.
If the value of the signal (SignalSource) during the Trigger Event is outside the
permissible value range and outside the zone between StartIgnore and
StopIgnore (Ignore zone), the module will report an error, the RecordesSignal is
updated.
Within this range, the signals are read in with a temporal exactitude of <1µs
(determined by linear interpolation).
If a Trigger Signal occurs at Execute = False, the RecordedSignal is not
updated.
If no Trigger Signal comes up, Busy remains active until the module is reset to
the original state with Abort.
More examples with C3_Touchprobe (example 7 (see page 279) and example 8
(see page 281)).