6.6 UPS Control
The UPS (Smart UPS series from APC) are controlled by a software pack-
age called “PowerChute plus” by APC. The software warns the user
against power problems and shuts down the D950 system smoothly and
with all vital data intact, whether an operator is present or not. In order to
guarantee proper operation, the PowerChute parameters (pwrchute.ini file)
should be set according to the following example:
[ Ups ]
SignallingType = Smart
PortName = COM11
AutoUpsRebootEnabled = Yes
CableType = Normal
[ EventLogging ]
EventLogEnabled = Yes
EventLogMaxSize = 50000
EventLogName=C:\PWRCHUTE\pwrchute.log
[ DataLogging ]
DataLogEnabled = Yes
DataLogMaxSize = 50000
DataLogInterval = 600
DataLogName=C:\PWRCHUTE\pwrchute.dat
[ ErrorLogging ]
ErrorLogEnabled = Yes
ErrorLogMaxSize = 50000
ErrorLogName=C:\PWRCHUTE\pwrchute.err
[ Messaging ]
MessageDelay = 1
MessageInterval = 30
[ SelfTests ]
EnableSelfTests = No
SelfTestDay = MONDAY
SelfTestSchedule = At turn on
SelfTestTime = 12:00 PM
LastSelfTestDay = 01/26/98
LastSelfTestResult = Passed
[ Shutdown ]
ShutdownDelay = 30
AdminShutdownDelay = 900
DailyShutdownEnabled = No
DailyShutdownTime = 6:00 PM
DailyWakeupTime = 7:00 AM
WeeklyShutdownEnabled = No
WeeklyShutdownDay = Friday
WeeklyShutdownTime = 6:00 PM
WeeklyWakeUpDay = Monday
WeeklyWakeUpTime = 7:00 AM
[ Server ]
Security = No
HostName =
[ UserInterface ]
TemperatureUnits = Celsius
SoundEffects = No
BARGRAPHType = Battery Capacity