10.3.2 VIEWING METER TOTALIZERS
From the View Totalizers Menu, select Meters. After selecting the preset and meter, the Meter Totalizers screen
displays:
Parameter Descriptions
Total Gross
Total gross volume through the flow meter.
Authorized Gross
Total authorized gross volume through the flow meter.
Unauthorized Gross
Total unauthorized gross volume through the flow meter.
Meter Creep Gross
Gross amount of volume designated as meter creep. Meter creep volumes are small
amounts of volume that have been indicated by the meter when flow is supposed to
be idle. Meter creep can be caused by a small leak, excessive line shock or electro-
magnetic interference.
Backflow Gross
Total gross volume that has flowed through the meter backwards. This can only be
detected with meters using dual pick-offs.
PRE #1 MTR #1 TOTALIZERS
Total Gross:0000006.31 0000006.31
Authorized Gross:0000006.31 0000006.31
Unauthorized Gross:0000000.00 0000000.00
Meter Creep Gross:0000000.00 0000000.00
Backflow Gross:0000000.00 0000000.00
CLeaR Next Prev Exit
PRE #1 MTR #1 TOTALIZERS
Total Gross:000000631 (000000631)
Authorized Gross:000000631 (000000631)
Unauthorized Gross:000000000 (000000000)
Meter Creep Gross:000000000 (000000000)
Backflow Gross:000000000 (000000000)
CLeaR Next Prev Exit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toptech Systems MultiLoad II and is the answer not in the manual?

Toptech Systems MultiLoad II Specifications

General IconGeneral
BrandToptech Systems
ModelMultiLoad II
CategoryControl Unit
LanguageEnglish

Related product manuals