365-575-102 Circuit Order: NTP-016
Issue 8.0, July 2002 Page 3 of 6
5. Did the command in Step 4 execute?
If YES, then go to Step 7.
If NO, then continue with Step 6.
6. Use the FAULT-Retrieve-Alarm command
to check for system alarms. Clear any alarms
present, then repeat this procedure from Step 4.
You must determine why the SWITCH command
in Step 4 did not execute before continuing this
procedure.
7.
NOTE:
Steps 7 through 13 assume that the
far-end node B NE is an FT-2000. If this is
not the case, then the equivalent sequence
of commands, which are appropriate for
the particular product, must be performed.
At CIT, remotely Login to far-end node B. Use
FAULT-Retrieve-State command to obtain
a report that lists the actual protection Switch
State of the OC-3 circuit packs.
If Service slot _a Switch State is active
(rx:act),gotoStep11.
If Service slot _a Switch State is
standby (rx:stby), then continue with
Step 8.