EasyManua.ls Logo

Parker Compax3 Fluid T40

Parker Compax3 Fluid T40
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
C3F_T40
456 192-121102 N04 June 2008
Environmental requirements Compax3F
General ambient conditions
According to EN 60 721-3-1 to 3-3
Climate (temperature/humidity/barometric
pressure): Class 3K3
Permissible ambient temperature:
Operation
Storage
Transport
0 to +45 C Class 3K3
-25 to +70 C Class 2K3
–25 to +70 C Class 2K3
Tolerated humidity:
No condensation
Operation
Storage
Transport
<= 85% class 3K3
<= 95% class 2K3
<= 95% class 2K3
(Relative humidity)
Elevation of operating site
<=1000m above sea level for 100% load
ratings
<=2000m above sea level for 1% / 100m
power reduction
Please inquire for greater elevations
Mechanic resonances:
EN 60068-2-6 (sinusoidal excitation)
Sealing
IP20 protection class according to EN 60 529
Insulation requirements
Degree of contamination
Level of contamination 2 according to EN 50 178
UL certification
conform to UL:
USL according to UL508 (Listed)
CNL according to C22.2 No. 142-
M1987. (Listed)
Certified
E-File_No.: E198563
The UL certification is documented by a ”UL” logo on the
device (type specification plate).
”UL” logo

Table of Contents

Related product manuals