List of Parameters
Parameters
1-103
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the status of analog outputs.
Note: AO: Analog Output
Description: Sets the simulation mode for digital inputs.
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
DI: Digital Input
T: Terminal
Description: Sets the simulation mode for digital inputs.
Dependency: The setpoint for the input signals is specified using p0796.
Refer to: p0796
Note: This parameter is not saved when data is backed up (p0971).
DI: Digital Input
T: Terminal
r0785.0...1 BO: CU analog outputs status word / CU AO ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 AO 0 negative Yes No -
01 AO 1 negative Yes No -
p0795 CU digital inputs simulation mode / CU DI simulation
CU240B-2
CU240B-2 DP
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) Simulation Terminal eval. -
01 DI 1 (T. 6) Simulation Terminal eval. -
02 DI 2 (T. 7) Simulation Terminal eval. -
03 DI 3 (T. 8) Simulation Terminal eval. -
11 DI 11 (T. 3, 4) AI 0 Simulation Terminal eval. -
p0795 CU digital inputs simulation mode / CU DI simulation
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) Simulation Terminal eval. -
01 DI 1 (T. 6) Simulation Terminal eval. -
02 DI 2 (T. 7) Simulation Terminal eval. -
03 DI 3 (T. 8) Simulation Terminal eval. -
04 DI 4 (T. 16) Simulation Terminal eval. -
05 DI 5 (T. 17) Simulation Terminal eval. -
11 DI 11 (T. 3, 4) AI 0 Simulation Terminal eval. -
12 DI 12 (T. 10, 11) AI 1 Simulation Terminal eval. -