EasyManua.ls Logo

Siemens SINAMICS G120 - Fig. 2-37 2454 - ZSW3 status word interconnection (p2038 = 0)

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication
Function diagrams
2-535
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-37 2454 – ZSW3 status word interconnection (p2038 = 0)
- 2454 -
Function diagram
87654321
FP_2454_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU240B/E-2 DP
13.12.2010 V4.4
ZSW3 status word interconnection (p2038 = 0)
<1>
ZSW3.0
ZSW3.1
ZSW3.2
ZSW3.3
ZSW3.4
ZSW3.5
ZSW3.6
ZSW3.8
ZSW3.9
ZSW3.11
ZSW3.12
ZSW3.13
ZSW3.14
ZSW3.15
ZSW3.7
ZSW3.10
p2051[3] = r0053
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
[2511.7]
-
-
-
[2511.7]
[2511.7]
-
-
-
-
-
<1>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Signal sources for ZSW3 im Interface Mode SINAMICS (p2038 = 0)
Signal
Meaning
Interconnection
parameters
[Function diagram]
internal status word
[Function diagram]
signal source
Inverted
Used in telegrams 350.
1 = DC brake active
0 = DC brake not active
1 = |n_act| > p1226 (n_standstill)
1 = |n_act| > p1080 (n_min)
1 = I_act >= p2170
1 = |n_act| > p2155
1 = |n_act| <= p2155
1 = |n_act| >= r1119 (f_set)
1 = Vdc <= p2172
1 = Vdc > p2172
1 = Ramping finished
1 = Techn. contr. out at lower limit
1 = Techn. contr. out at upper limit
Reserved
Reserved
Reserved
Reserved
[7017.5]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[2534.7]
[3080.7]
[7958.7]
[7958.7]