List of Parameters
Parameters
1-461
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the y-coordinates for the breakpoints (B0...B19) of the polyline (20 breakpoints) of instance PLI 0.
Index: [0] = Breakpoint 0
[1] = Breakpoint 1
[2] = Breakpoint 2
[3] = Breakpoint 3
[4] = Breakpoint 4
[5] = Breakpoint 5
[6] = Breakpoint 6
[7] = Breakpoint 7
[8] = Breakpoint 8
[9] = Breakpoint 9
[10] = Breakpoint 10
[11] = Breakpoint 11
[12] = Breakpoint 12
[13] = Breakpoint 13
[14] = Breakpoint 14
[15] = Breakpoint 15
[16] = Breakpoint 16
[17] = Breakpoint 17
[18] = Breakpoint 18
[19] = Breakpoint 19
Description: Setting parameter for the run-time group in which instance PLI 0 of the polyline is to be called
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance PLI 0 within the run-time group set in p20376.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20375[0...19] PLI 0 Y-coordinate, B breakpoint / PLI 0 Y-coordinate
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
-340.28235E36 340.28235E36 0.0000
p20376 PLI 0 run-time group / PLI 0 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
5 9999 9999
p20377 PLI 0 run sequence / PLI 0 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 32000 980