Siemens SINAMICS G120 - r9772.0...20 CO;BO: SI status (processor 1); SI status P1; r9773.0...31 CO;BO: SI status (processor 1 + processor 2); SI status P1+P2

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-372
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the Safety Integrated status on processor 1.
Dependency: Refer to: r9872
Note: Re bit 00:
When STO is selected, the cause is displayed in bits 16 ... 20.
Re bit 18:
When the bit is set, STO is selected via PROFIsafe.
Re bit 19:
For the drive-integrated motion monitoring functions, due to OFF2, no actual value sensing possible.
Description: Displays the Safety Integrated status on the drive (processor 1 + processor 2).
Note: This status is formed from the AND operation of the relevant status of the two monitoring channels.
r9772.0...20 CO/BO: SI status (processor 1) / SI status P1
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO selected on processor 1 Yes No 2810
01 STO active on processor 1 Yes No 2810
09 STOP A cannot be acknowledged, active Yes No 2802
10 STOP A active Yes No 2802
15 STOP F active Yes No 2802
16 STO cse: Safety comm. mode Yes No -
17 STO cause selection via terminal (Basic
Functions)
Yes No -
18 STO cause: Selection via motion monitoring
functions
Yes No -
19 STO cause actual value missing Yes No -
20 STO cause selection PROFIsafe (Basic
Functions)
Yes No -
r9773.0...31 CO/BO: SI status (processor 1 + processor 2) / SI status P1+P2
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO selected in drive Yes No 2804
01 STO active in drive Yes No 2804
31 Shutdown paths must be tested Yes No 2810