Loading...
Input/Output Terminals
Function diagrams
2-513
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Fig. 2-18 9567 – CU240B-2: Analog input 0 (AI0)
- 9567 -
Function diagram
87654321
FP_9567_97_02.vsd
External Interfaces
G120 CU240B-2
13.12.2010 V4.4
Analog input 0 (AI0)
3
3
20 mA
T0
<2>
0  20 mA
-10  +10 V
Kl.3
[%]
xy
<2> <2>
A
D
+
-
<1>
<1>
x
1
y
2
x
2
y
1
y
x
[%]
Bezugsgrößen
p2000...r2004
y
x
2
x
1
<2> <3>
% 100
xx
21
<3>
I
1
0
20 mA
1
0
Voltage
Current
Hardware smoothing
100 μs
Scaling
Differential input!
For an input signal referred to ground, terminal 4 must be connected to reference potential M.
Caution:
The voltage between an input (Kl.3 (Kl.10) or Kl.4 (Kl.11)) and the ground point must not exceed 35 V.
When the load resistor is switched in (DIP switch in position I), the voltage between the input terminals
must not exceed 10 V or the impressed current 80 mA.
For p0756 = 2, 3 the units are mA.
For p0756 = 0, 1, 4 the units are V.
Possible settings p0756[0]:
= 0: 0 V ... +10 V
= 1: +2 V ... +10 V with monitoring
= 2: 0 mA ... +20 mA
= 3: 4 mA ... +20 mA with monitoring
= 4: -10 V ... +10 V (Default for AI0)
F03505
"Wire
breakage"
r0752
CU AI U/I_inp act
Kl.4
<4>
Wire breakage sensing only activated when p0756 = 1, 3.
Kl. = Terminal
Sampling time of the AI : 4 ms
r0755
CU AI value in % [%]
[0]
<2>
<4>
<2>
Type switching
Analog input
U I
U
AI0
U I
AI0
CU AI status word
r0751
CU WireBrkThresh
0.00 ... 20.00
p0761[0..1] (2.00)
CU wire brk t_del
0 ... 1000 [ms]
p0762[0..1] (100)
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
CU AI sim setp
-50.000 ... 2000.000
p0798[0..1] (0.000)
CU AI char y1
-1000.00 ... 1000.00 [%]
p0758[0..1] (0.00)
CU AI char y2
-1000.00 ... 1000.00 [%]
p0760[0..1] (100.00)
CU AI char x1
-50.000 ... 160.000
p0757[0..1] (0.000)
CU AI char x2
-50.000 ... 160.000
p0759[0..1] (10.000)
CU AI T_smooth
0.0 ... 1000.0 [ms]
p0753[0..1] (0.0)
[0] (0)
[0] (2.00)
[0] (10.000)
[0] (100)
[0] (0.000)
[0] (0.0)
[0] (0.00)
[0] (100.00)
[0] (0.000)
CU AI type
0 ... 8
p0756[0..1] (4)
[0] (4)
CU AI sim_mode
0 ... 1
p0797[0..1] (0)
[0] (0)