Siemens SINAMICS G120 - r0623 Stator resistance of Rs identification after powering up again; R_Stator Reset_Id; p0625[0...n] Motor ambient temperature; Mot T_ambient; p0626[0...n] Motor overtemperature, stator core; Mot T_over core; p0627[0...n] Motor overtemperature, stator winding; Mot T_over stator

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-84
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the identified stator resistance after the Rs identification after powering up again.
Dependency: Refer to: p0621, p0622
Description: Defines the ambient temperature of the motor for calculating the motor temperature model.
Note: The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
Description: Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency: For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
r0623 Stator resistance of Rs identification after powering up again / R_Stator Reset_Id
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0625[0...n] Motor ambient temperature / Mot T_ambient
Access level: 3 Calculated: p0340 = 1,2 Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_1 Unit selection: p0505
Min Max Factory setting
-40 [°C] 80 [°C] 20 [°C]
p0626[0...n] Motor overtemperature, stator core / Mot T_over core
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_2 Unit selection: p0505
Min Max Factory setting
20 [K] 200 [K] 50 [K]
p0627[0...n] Motor overtemperature, stator winding / Mot T_over stator
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: C(3), U, T Scaling: - Data set: MDS
Units group: 21_2 Unit selection: p0505
Min Max Factory setting
20 [K] 200 [K] 80 [K]