Siemens SINAMICS G120 - p1336[0...n] Slip compensation limit value; Slip comp lim val; r1337 CO: Actual slip compensation; Slip comp act val; p1338[0...n] U;f mode resonance damping gain; Uf Res_damp gain; p1339[0...n] U;f mode resonance damping filter time constant; Uf Res_damp T

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-192
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the limit value for slip compensation in [%] referred to r0330 (motor rated slip).
Description: Displays the actual compensated slip [%] referred to r0330 (rated motor slip).
Dependency: p1335 > 0 %: Slip compensation active.
Refer to: p1335
Description: Sets the gain for resonance damping for U/f control.
Dependency: Refer to: p1300, p1339, p1349
Note: The resonance damping function dampens active current oscillations that frequency occur under no-load condi-
tions.
The resonance damping is active in a range of approximately 5 ... 90 % of the rated motor frequency (p0310), but
up to a maximum of 45 Hz.
For the open-loop control modes p1300 = 5 and 6 (textile sectors), the resonance damping is internally disabled in
order that the output frequency can be precisely set.
Description: Sets the filter time constant for resonance damping for U/f control.
Dependency: Refer to: p1300, p1338, p1349
p1336[0...n] Slip compensation limit value / Slip comp lim val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 [%] 600.00 [%] 250.00 [%]
r1337 CO: Actual slip compensation / Slip comp act val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- [%] - [%] - [%]
p1338[0...n] U/f mode resonance damping gain / Uf Res_damp gain
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 0.00
p1339[0...n] U/f mode resonance damping filter time constant / Uf Res_damp T
Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
1.00 [ms] 1000.00 [ms] 20.00 [ms]