Fig. 2-31 2441 – STW1 control word interconnection
- 2441 -
Function diagram
87654321
FP_2441_97_61.vsd
PROFIdrive / PROFIBUS
G120 CU240B/E-2 DP
13.12.2010 V4.4
STW1 control word interconnection (p2038 = 2)
<1>
STW1.0
STW1.1
STW1.2
STW1.3
STW1.4
STW1.5
STW1.6
STW1.8
STW1.9
STW1.11
STW1.12
STW1.13
STW1.14
STW1.15
STW1.7
STW1.10
p0848[0] = r2090.2
p0852[0] = r2090.3
p2103[0] = r2090.7
-
-
p0854[0] = r2090.10
p1113[0] = r2090.11
-
-
-
p0810[0] = 2090.15
<3>
p0840[0] = r2090.0
p0844[0] = r2090.1
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2546.1]
-
-
[2501.3]
[2505.3]
-
-
-
-
[2501.3]
[2501.3]
[8060]
-
-
[2501]
[3040]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
<2>
<2>
<1>
Signal targets for STW1 in Interface Mode VIK-NAMUR (p2038 = 2)
Signal
Meaning
Interconnection
parameters
[Function diagram]
internal control
word
[Function diagram]
signal target
Inverted
= ON (pulses can be enabled)
0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on)
1 = No OFF2 (enable is possible)
0 = OFF2 (immediate pulse suppression and switching on inhibited)
1 = No OFF3 (enable is possible)
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse suppression and switching on inhibited)
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
0 = Inhibit setpoint (set the ramp-function generator input to zero)
= Acknowledge faults
Reserved
Reserved
Reserved
Reserved
Reserved
1 = Control via PLC
1 = Dir of rot reversal
1 = CDS selection
Used in telegram 20.
Bit 10 in STW1 must be set to ensure that the drive accepts the process data.
Sequence control
Sequence control
Sequence control
Sequence control
<3>
Interconnection is not disabled.
[3060] [3070] [3080]
[3060] [3070]
[3060] [3070] [3080]
[8565]
p1140[0] = r2090.4
p1141[0] = r2090.5
p1142[0] = r2090.6