EasyManua.ls Logo

Siemens SINAMICS G120 - p0500 Technology application; Tec application

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-74
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0340 = 5.
Value: 0: Standard drive
1: Pumps and fans
2: Sensorless closed-loop control down to f = 0 (passive loads)
3: Pumps and fans, efficiency optimization
Notice: If the technological application is set to p0500 = 0 ... 3 during commissioning (p0010 = 1, 5, 30), the operating mode
(p1300) is pre-set accordingly.
Note: The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5
For p0500 = 0 and when the calculation is initiated, the following parameters are set:
- p1574 = 10 V
- p1750 bit 2 = 0
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0, PM260: p1802 = 2)
- p1803 = 106 % (PM260: p1803 = 103 %)
For p0500 = 1 and when the calculation is initiated, the following parameters are set:
- p1574 = 2 V
- p1750 bit 2 = 0
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0)
- p1803 = 106 % (PM260: p1803 = 103 %)
For p0500 = 2 and when the calculation is initiated, the following parameters are set:
- p1574 = 2 V (for separately-excited synchronous motors: 4 V)
- p1750 bit 2 = 1
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0)
- p1803 = 106 % (PM260: p1803 = 103 %)
For p0500 = 3 and when the calculation is initiated, the following parameters are set:
- p1574 = 2 V
- p1750 bit 2 = 1
- p1802 = 4 (SVM/FLB without overcontrol) (PM240: p1802 = 0)
- p1803 = 106 % (PM260: p1803 = 103 %)
Re p1750:
The setting of p1750 is only relevant for induction motors.
p1750 bit 2 = 1: Sensorless closed-loop control of induction motors effective up to a frequency of zero.
This operating mode is possible for passive loads. These include applications where the load does not generate
regenerative torque when breaking away and the motor comes to a standstill (zero speed) itself when the pulses
are inhibited.
Re p1802 / p1803:
p1802 and p1803 are only changed, in all cases, if a sine-wave output filter (p0230 = 3, 4) has not been selected.
p0500 Technology application / Tec application
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C(1, 5), T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 3 0

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals