EasyManua.ls Logo

Siemens SINAMICS G120 - r2135.12...15 CO;BO: Status word faults;alarms 2; ZSW fault;alarm 2; r2136[0...63] Fault time removed in days; t_flt resolv. days; r2138.7...15 CO;BO: Control word faults;alarms; STW fault;alarm

Siemens SINAMICS G120
750 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-282
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: Displays the second status word of faults and alarms.
Description: Displays the system runtime in days when the fault was removed.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133
Notice: The time comprises r2136 (days) and r2109 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the control word of the faults and alarms.
Dependency: Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
r2135.12...15 CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
12 Fault motor overtemperature Yes No -
13 Fault power unit thermal overload Yes No -
14 Alarm motor overtemperature Yes No -
15 Alarm power unit thermal overload Yes No -
r2136[0...63] Fault time removed in days / t_flt resolv. days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
r2138.7...15 CO/BO: Control word faults/alarms / STW fault/alarm
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Acknowledge fault Yes No -
10 External alarm 1 (A07850) effective Yes No -
11 External alarm 2 (A07851) effective Yes No -
12 External alarm 3 (A07852) effective Yes No -
13 External fault 1 (F07860) effective Yes No -
14 External fault 2 (F07861) effective Yes No -
15 External fault 3 (F07862) effective Yes No -