Parameters
List of Parameters
1-322
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Description: The function of the 2-3-WIRE Control Command 1 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
Description: The function of the 2-3-WIRE Control Command 2 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
Description: The function of the 2-3-WIRE Control Command 3 depends on the selected 2-3-WIRE type. It shall be predefined
by p0015
Description: The output values of the 2-3-WIRE Control Command depends on the selected 2-3-WIRE type and the control
command inputs. Type shall be predefined by p0015
Description: Determines the 2/3-Wire type using the terminals. It shall be predefined by p0015.
Value: 0: No 2/3-Wire control
1: 2-Wire Forward-Backward 1
2: 2-Wire Forward-Backward 2
3: 3-Wire Enable-Forward-Backward
4: 3-Wire Enable-On-Reverse
p3330[0...n] BI: 2-3-WIRE Control Command 1 / 2-3-WIRE CC_1
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3331[0...n] BI: 2-3-WIRE Control Command 2 / 2-3-WIRE CC_2
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
p3332[0...n] BI: 2-3-WIRE Control Command 3 / 2-3-WIRE CC_3
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: U, T Scaling: - Data set: CDS, p0170
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r3333.0...3 CO/BO: 2-3-WIRE Output / 2-3-WIRE OUT
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 2-3-Wire On Yes No -
01 2-3-Wire Reverse Yes No -
02 2-3-Wire On/Inverse Yes No -
03 2-3-Wire Reverse/Inverse Yes No -
p3334 2-3-WIRE Selection / 2-3-WIRE Sel
Access level: 4 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 4 0